Uni Gris Quartz

CORE – Quartz grey

GREENOR Fancoil

Simplicity and sobriety

Retailer Find a retailer Contact
  • S-03 Quartz grey
  • S-03 Quartz grey

Simplicity and sobriety

CORE – Quartz grey

GREENOR Fancoil Solid

Minimalist aesthetics, CORE models can be patinated in Quartz Grey, Olycal White and other pigments on request.

GREENOR is a new generation architectural hydronic fan coil unit designed for visible installation in high-end residential and hospitality environments. Units operate on hydronic heating and cooling loops supplied by air-to-water heat pumps or central chilled water systems. Ultra-quiet, draft-free comfort for high-end residential and hospitality projects.

Delivering up to 10,000 BTU/h (3 kW) of cooling capacity per unit — CORE GREENOR connects to an air-to-water heat pump or a chilled-water network.

Ultra quiet

Draught-free and ultra-quiet for an exceptional climate

greenor chaud froid

Heating/Cooling

Allows heating or air conditioning with Air/Water heat pump (chilled water technology) pump (chilled water technology).

Anti-viral exchanger / UV filter

Purifies air during a pandemic in less than 2 hours. Patented 100% copper vertical exchanger.

Greenor heating only

Hawaii 9

Works like a very high-power radiator (3740W) for existing boilers or air-water heat pumps

Greenor Reversible

Hawaii 7

Identical to the Greenor Heating only with air-conditioning option (1600W). Perfect comfort, very even & incredibly quiet

  • Submittal Sheet

    General Description
    GREENOR is a new generation architectural hydronic fan coil unit designed for visible
    installation in high-end residential and hospitality environments. Units operate on
    hydronic heating and cooling loops supplied by air-to-water heat pumps or central
    chilled water systems. Ultra-quiet, draft-free comfort for high-end residential and
    hospitality projects.
    Key Features:
    • Ultra-low air velocity (0.14–0.51 ft/s)
    • Integrated 3-way control valve (24V)
    • Low voltage internal components (24V) – Integrated UL-listed transformer
    • Designed with UL / ETL recognized components
    • Designed for low-temperature hydronic systems (heat pumps)
    Applications:
    • High-end residential
    • Hospitality
    • Luxury apartments

    Airflow Concept & Comfort :
    GREENOR units operate as free‑return hydronic terminals. Air is gently drawn through
    the heat exchanger and discharged vertically along the front surface.
    This creates a natural convection effect, ensuring smooth and homogeneous air
    distribution throughout the room.
    The low velocity avoids discomfort while maintaining effective heating and cooling
    performance.
    This ultra‑low velocity diffusion concept minimizes draft and improves acoustic comfort
    Greenor :

    Hydronic Connections
    • System Type: 2-pipe hydronic system
    • Supply Connection: 1/2″ (or specify)
    • Return Connection: 1/2″ (or specify)
    • Factory-integrated 3-way control valve (24V)
    • Recommended accessories: air vent, balancing valve, isolation valves
    • Condensate drain connection (cooling mode): gravity drain or optional condensate
    pump
    Electrical Connections
    • Power Supply: 120V / 60Hz (or project-specific)
    • Internal transformer: 120V to 24V (UL listed)
    • All internal components operate at 24V (fans, valve, controls)
    • Low voltage thermostat connection (24V)
    • Compatible with standard HVAC control systems
    Notes
    All connections to be performed by licensed professionals.
    Refer to project specifications for final selection and installation details.
    Consult CINIER engineering for custom configurations.

    Unit Dimensions & Clearances
    Model Dimensions (W x D x H) Weight
    GREENOR 21.25″ x 4.5″ x 74.8″ 127.8 lb
    GREENOR XL 21.25″ x 5.8″ x 74.8″ 143.3 lb
    Minimum Installation Clearances
    Top: 4 in
    Bottom: 4 in
    Sides: 12 in (recommended for airflow)
    Front: 12 in (recommended for airflow and service access)

    Condensate Management
    Integrated condensate drain pan
    Gravity drain connection
    Optional condensate pump available
    Condensed water volume : 0.18 gallon / hour

    Compliance
    • Designed in accordance with UL / ETL safety standards
    • Uses UL / ETL recognized components
    • Electrical components selected in accordance with UL / CSA requirements
    • Integrated UL-listed transformer
    • Designed for integration into systems complying with ASHRAE comfort and HVAC
    design guidelines
    • Suitable for installation in accordance with IMC (International Mechanical Code)

    Heating Performance – Heat Pump Conditions (AHRI-style)
    Entering Air: 70°F DB / 67°F WB
    Entering Water: 120°F
    Leaving Water: 100°F
    Designed for modern low-temperature heating systems.
    GREENOR Heating
    Fan Speed CFM BTU/h GPM    psi kPa    dB(A)
    Low             67      4196      1.19   0.13 0.90    14.8
    Medium    114     7506      1.19     0.23 1.59    25.6
    High           169    12761    1.19     0.46 3.17    35.7
    GREENOR XL Heating
    Fan Speed CFM   BTU/h    GPM    psi kPa    dB(A)
    Low              171   7441     1.76       0.89 6.14   25.2
    Medium     280   13590    1.76        1.66 11.45     36.3
    High            339   23270    1.76     2.16 14.89     40.8

    Hydronic Data
    Parameter GREENOR GREENOR XL
    System Type 2-pipe hydronic loop 2-pipe hydronic loop
    Typical Water
    Flow ~1.2 GPM ~1.8 GPM
    Pressure Drop 0.13 – 0.46 psi 0.89 – 2.16 psi
    (0.9 – 3.2 kPa) (6.1 – 14.9 kPa)

    Cooling Performance (AHRI-style)
    Entering Air: 80°F DB / 67°F WB
    Entering Water: 45°F
    Leaving Water: 55°F

    GREENOR
    Fan Speed    CFM   BTU/h GPM   psi kPa dB(A)
    Low               67       2184     1.19   0.13 0.90 14.8
    Medium      114       4094     1.19   0.23 1.59 25.6
    High           169       5459      1.19    0.46 3.17 35.7

    GREENOR XL
    Fan Speed    CFM    BTU/h    GPM   psi kPa   dB(A)
    Low               171      5050       1.76     0.89 6.14   25.2
    Medium      280      6995        1.76     1.66 11.45   36.3
    High             339     10277      1.76    2.16 14.89   40.8
    Airflow values measured at nominal conditions.
    Low airflow design optimized for ultra-quiet operation and architectural integration.

    Sound Level
    Model Fan Speed Sound Level
    GREENOR Low 14.8 dB(A)
    GREENOR Medium 25.6 dB(A)
    GREENOR High 35.7 dB(A)
    GREENOR XL
    Low
    25.2 dB(A)
    GREENOR XL Medium 36.3 dB(A)
    GREENOR XL High 40.8 dB(A)
    Sound data: according to ISO 11203, measured at 1.09 yd (1 m)

    Electrical Data
    • 24V low-voltage internal components (fans, valves, controls)
    • Integrated UL-listed transformer (110/240 V to 24 Volts)
    • Integrated Honeywell 3‑way control valve with 24V actuator
    • UL / ETL listed components (Intertek)
    • Power Supply: 120V / 60Hz (or project-specific)

    Made in France

  • Basis of Design Specification
      • Architectural Hydronic Fan Coil Units
        Basis of Design Product: CINIER GREENOR Architectural Hydronic Fan Coil Unit.
        The system shall provide ultra-low velocity air diffusion, silent operation suitable for
        luxury residential spaces, and architectural visible installation.
        The unit shall incorporate:
        • Factory integrated Honeywell 3-way hydronic control valve (24V)
        • Internal UL-listed transformer supplying all internal components
        • Low voltage 24V electrical architecture
        • Ultra-low air velocity diffusion system
        • Ultra-quiet fan operation suitable for residential environments
        • Compatibility with air-to-water heat pump hydronic systems
        Equivalent products must demonstrate compliance with all architectural, acoustic, and
        hydronic performance characteristics described in this specification
      • Greenor® is listed:

        CE norms: EN 60335-2-30, EN 55014-1 (Ed 2006), EN 61000-3-2 (Ed2006) and EN 61000-3-3/A1 (Ed 1995/01): for the European markets.
        UL 1995, issue:2011/10/14 Ed:4 UL Standard for Safety Heating and Cooling Equipment for the US market.
        CSA C22.2 No. 236, issue:2011/10/14 Ed:4 Heating and Cooling Equipment for the Canadian market.

  • Installation

    Required 2 person or 1 person with the appropriate mounting tools.

    Connection to be made by a professional (plumber HVAC specialist).

    Connection center: 4 cm – Installation instructions on request.

    → Drawing of installation

    Access to Components
    • Front panel removable or security door for service access
    • Direct access to:
    – Fans
    – Hydronic coil
    – 3-way control valve (factory integrated)
    – Electrical components (24V)
    • Simplified internal layout for quick servicing
    Hydronic System Maintenance
    • Standard 2-pipe hydronic connections
    • Integrated control valve reduces external components
    • Compatible with standard HVAC maintenance procedures

    Service Benefits
    • Reduced maintenance frequency
    • Easy access without unit removal
    • No complex disassembly
    • Designed for residential and high-end applications

    Engineering Note
    GREENOR units are engineered to minimize service interventions while maintaining
    optimal performance. The combination of low airflow operation and simplified
    component access ensures long-term operational reliability.

    Installation Guidelines
    • Installation shall be performed by qualified professionals.
    • Due to unit size and weight, handling by two installers is recommended.
    • Wall structure must be verified for load-bearing capacity prior to installation.
    • Ensure adequate clearances for airflow and service access.
    • All hydronic and electrical connections must comply with local codes.
    Unit must be installed in accordance with project specifications and local building codes.

     

Add to a wishlist

My wishlists
Or

Create a new list in order to add products.